Our wide range of products includes Field Communicator, Pressure transmitters, Temperature transmitters, Flow Meters, DCS etc.

8C-TCNTA1 | Series 8 C300 Controller IOTA

  • Specifications


    Experion Series 8 · C300 controller termination
    IOTA · passive connectors · serves 8C-PCNTxx

    8C-TCNTA1 — Honeywell Series 8 C300 Controller IOTA (Not the Controller Module)

    8C-TCNTA1 is the coated Series 8 C300 Controller I/O Termination Assembly. S803-150-520, section 3.2, lists it beside the controller electronics, not as the controller itself. The C300 is built as a two-piece set: the electronics module plugs onto this IOTA. Honeywell states that the C300 IOTA holds only passive devices — FTE address switches, FTE cable connectors, and I/O Link cable connectors. The processor, CEE execution, and memory belong to the module that sits on it, in current documentation 8C-PCNT03. HKXY Instruments is a China industrial automation trader, not Honeywell, and does not list stock or a price here.

    Controller IOTA identity

    Item Documented reference (S803-150-520)
    Manufacturer Honeywell
    Exact model 8C-TCNTA1
    Honeywell description Series 8 C300 Controller I/O Termination Assembly (IOTA), coated
    Electronics it serves Series 8 C300 controller modules in the 8C-PCNTxx family; the current coated controller listed in this specification is 8C-PCNT03
    What is on the IOTA Passive devices only: FTE address switches, FTE cable connectors, and I/O Link cable connectors
    IOTA size (controller) 220 mm (9 in) height, 120 mm (4.75 in) width
    Redundancy hardware A redundant C300 uses a second controller, a second IOTA, and redundancy cable 51305980-836
    I/O Link connectors Two I/O Link interfaces, which are redundant, are on this IOTA and connect the controller to Series 8 I/O
    Material number [TO CONFIRM] from the nameplate

    Do not order this IOTA when the failed part is the controller — or a Series C C300

    If the nameplate on the plug-in electronics reads 8C-PCNT03, the inquiry belongs on that controller page, not here. This termination does not execute control strategies, hold the 16 MB program memory, or provide the dual 100 Mbps FTE uplinks by itself; those functions are specified for the controller module. Conversely, replacing only the electronics and leaving a damaged 8C-TCNTA1 in the cabinet will not restore FTE addressing or I/O Link connectors.

    A second distinction matters for searchers coming from Series C spares: CC-PCNT02 is the Experion PKS Series C C300 controller module, and its IOTA is a Series C part (CC-TCNT01 in the documentation used for that rewrite). 8C-TCNTA1 is the Series 8 termination and is not a substitute for that Series C pair. Do not treat “PCNT” as a universal controller SKU.

    What to confirm on an 8C-TCNTA1 request

    • Photograph the IOTA nameplate (8C-TCNTA1) and the controller module that plugs into it (typically 8C-PCNT03; do not assume 8C-PCNT05 or a Series C CC-PCNTxx without reading the label).
    • Say whether the station is non-redundant or already uses a second IOTA plus cable 51305980-836.
    • Note FTE address-switch settings and which I/O Link cables land on the IOTA, so a replacement can be checked against the installed layout.
    • If memory backup is part of the station, treat the RAM charger assembly and its cables as separate line items ([TO CONFIRM] against the installed labels; the specification lists more than one charger-related number).
    • Condition, inspection, packing, lead time, and price remain [TO CONFIRM].

    Related Series 8 controller-family pages

    • 8C-PCNT03 — coated Series 8 C300 controller module that mounts on this IOTA
    • 8C-SHEDA1 — Series 8 header board that distributes 24 V and IOLink toward IOTAs in the cabinet
    • CC-PCNT02 — Series C C300 controller (different family; not a substitute)
    • Redundancy cable 51305980-836 (Honeywell listed part; confirm the installed cable before ordering)

    FAQ

    Is 8C-TCNTA1 the C300 controller?
    No. It is the coated Series 8 C300 controller IOTA. The controller electronics are a separate 8C-PCNTxx module.

    Which controller mounts on it?
    S803-150-520 lists 8C-PCNT03 as the current coated Series 8 C300 controller and notes that 8C-PCNT03 replaces 8C-PCNT02. Confirm the module actually seated on the IOTA; 8C-PCNT05 is a different SKU and is not specified here.

    Does the IOTA contain the FTE ports?
    Yes. Honeywell describes the C300 IOTA as the location of the FTE address switches, FTE cable connectors, and I/O Link cable connectors.

    Can I use a Series C controller IOTA instead?
    No. CC-TCNT01 (Series C) and 8C-TCNTA1 (Series 8) are not interchangeable on the evidence used for this page.

    Is the redundancy cable included?
    Not on this page. Honeywell lists 51305980-836 as a separate cable for two modules/IOTAs. Ask for it only if the station is redundant and that cable is required.

    Request a quote for 8C-TCNTA1

    Send photographs of the IOTA and the controller module, and say whether the station uses a redundancy cable. HKXY Instruments will confirm condition, inspection, packing, and lead time for the exact printed codes. We are not the OEM.

    Contact: Vicky · 86-18086430982 · vicky@hkxytech.com
    TOWER 707-713 NATHAN ROAD MONGKOK KOWLOON HONGKONG

    Request quote for 8C-TCNTA1

    Have any question, Please enter the form below and click the submit button.


    *
    *
    2 + 9 = ?
    Please enter the answer to the sum & Click Submit to verify your registration.
    CATEGORY AND TAGS:

    Honeywell

    Related Items

  • Product Categories

  • Why Us?

    1. 100% original product, 100% quality assurance.

    2. Varied payment methods.

    3.Safe & High-efficient shipping

  • Contact Us




    Contact: Vicky

    Mobile Phone: 86-18086430982
    Mail:vicky@hkxytech.com

    Address: TOWER 707-713 NATHAN ROAD MONGKOK KOWLOON HONGKONG