PGM · coated · FTE node
8C-IP0102 — Honeywell Series 8 PROFIBUS Gateway Module (Coated PGM)
Honeywell’s Series 8 Profibus Gateway Module specification (S803-160-110, Release 110, January 2014) identifies 8C-IP0102 as the coated PROFIBUS Gateway assembly — a communications gateway, not a process analog or discrete I/O card. The live pages on this site disagreed with each other: an older supplier URL called the part an “I/O Module,” while the later fresh URL called it an “interface component.” Those labels are dropped here. The documented mating termination is 8C-TPOXA1 (coated IOTA). The uncoated gateway assembly is 8U-IP0102, with uncoated IOTA 8U-TPOXA1. HKXY Instruments is a China industrial automation trader with 15 years of export experience, not the OEM, and this page does not list stock or a unit price.
Documented gateway identity
| Item | Official reference |
|---|---|
| Manufacturer | Honeywell |
| Exact model | 8C-IP0102 |
| Honeywell description | PROFIBUS Gateway ASSY, coated (S803-160-110) |
| Uncoated counterpart | 8U-IP0102 |
| Mating IOTA | 8C-TPOXA1, coated (8U-TPOXA1 uncoated). The PGM specification lists this IOTA as a 64-point PWA. |
| Supervisory network | The Series 8 PGM is a standard Fault Tolerant Ethernet (FTE) node. |
| Supply | 24 VDC; module current rating 430 mA |
| Mounting and power | Mounts on the standard Series 8 mounting assembly (on an IOTA), inside a standard Series 8 cabinet, and must use the standard Series 8 power system. |
| Removal under power | Module Removal and Insertion Under Power is supported. |
| Material number 51454362-275 | [TO CONFIRM] — this number appears in the older site URL and title, but it has not been read from a nameplate on this page. |
What the PGM specification actually covers
S803-160-110 describes the gateway as a PROFIBUS DP master on the field side and an FTE node on the Experion side. DP (V0) is supported, including standard and extended status bytes. For asset management, the PGM acts as a DP Master Class-2 device so Honeywell Field Device Manager (FDM) can reach DP slaves through vendor DTMs; that is the documented DPV1 path. DP (V2) is stated as not supported in release R110. HART devices hanging under PROFIBUS slaves can be reached through FDM when those slaves support HART. PROFIBUS PA is reached only through a third-party PA-to-DP converter or coupler. Media redundancy on the DP network, when used, relies on third-party redundancy link modules (the specification cites examples such as ABB RLM and Siemens Y Link). Simulation capability is not included in R110.
This gateway is how a Series 8 8C-PCNT03 C300 talks to PROFIBUS DP: the controller specification (S803-150-520) lists Profibus DP as “Via Profibus Gateway Module (PGM).” The PGM is not a substitute for a 4–20 mA output IOTA, a digital input card, or a Series C communications module. It also does not appear in the process I/O model table of S803-150-520; that I/O specification does not define 8C-IP0102, which is why this page cites the separate PGM document.
Procurement checks that actually matter for a PGM
- Photograph the nameplate so the printed code (8C-IP0102 versus 8U-IP0102), revision, and any material number can be read.
- Confirm whether the installed IOTA is 8C-TPOXA1 and whether the cabinet already has that termination in place.
- State the Experion / PlantCruise / LX release and whether FDM must reach the DP network.
- Note DP topology needs (PA coupler, slave redundancy, or a third-party link module) so the quotation is not treated as a generic “I/O module” spare.
- Availability, condition, inspection scope, packing, lead time, and price remain [TO CONFIRM] until that review is complete.
Related Series 8 communications pages
- 8C-TPOXA1 — coated IOTA documented for this PGM
- 8C-PCNT03 — Series 8 C300 controller that reaches Profibus DP through a PGM
- Experion spare overview
FAQ
Is 8C-IP0102 a process I/O module?
No. S803-160-110 calls it a PROFIBUS Gateway assembly. It does not take the place of a Series 8 analog or digital IOP.
Which termination does it use?
The coated IOTA is 8C-TPOXA1. The uncoated pair is 8U-IP0102 with 8U-TPOXA1. Do not assume an analog-output IOTA such as 8C-TAOXA1 will accept this gateway.
Does the older site material number 51454362-275 confirm the spare?
Not by itself. Treat that number as [TO CONFIRM] until it matches the installed nameplate.
Can this page promise DP V2 or built-in simulation?
No. The R110 specification states that DP V2 is not supported and that simulation is not provided in that release. Confirm the installed firmware and the current Honeywell document for the plant’s release.
How is this different from a Series C code with a similar IP prefix?
Series 8 and Series C hardware are not interchangeable by family name. Quote the exact 8C-IP0102 code and the mating 8C-TPOXA1 IOTA.
Request a quote for 8C-IP0102
Send a nameplate photograph, the installed IOTA code, and the Experion release that must host the PGM. HKXY Instruments will check condition, inspection, packing, and lead time against that exact code. We are not Honeywell.
Contact: Vicky · 86-18086430982 · vicky@hkxytech.com
TOWER 707-713 NATHAN ROAD MONGKOK KOWLOON HONGKONG