8C-PDODA1 | Series 8 Digital Output

  • Specifications


    Experion Series 8 · Bussed 24 V digital output IOP
    32 channels · 100 mA · coated

    8C-PDODA1 | Series 8 Digital Output (32-Channel, Bussed 24 V, Coated)

    8C-PDODA1 is the coated Series 8 digital output electronics module — the IOP — for bussed 24 VDC field loads such as solenoids and interposing relays. It is not a termination assembly. Honeywell mounts it on 8C-TDODA1 (9-inch non-redundant IOTA) or 8C-TDODB1 (12-inch redundant IOTA). The optional dry-contact path is a separate relay extension, 8C-SDOX01, used with the DO IOTA. HKXY Instruments is a China industrial automation trader with 15 years of export experience, not the OEM.

    Documented output ratings (S803-150-520 §4.4.10)

    Parameter Specification
    Module 8C-PDODA1 — digital output 24 VDC, field isolated, bussed output, coated
    IOTA 8C-TDODA1, 9-inch non-redundant; 8C-TDODB1, 12-inch redundant
    Channels / type 32; output type documented as source in the detailed table
    Load current 100 mA maximum per channel and 3.2 A maximum per module
    Load voltage 30 VDC maximum
    Module supply 24 VDC; module current rating 105 mA
    On-state voltage 24 VDC typical at 0.1 A maximum load current
    Off-state leak / switching 5 µA max leak; 10 ms max turn-on / turn-off; 0 ms output gap on redundant switchover
    Galvanic isolation 1000 VAC RMS or ±1500 VDC — the note states system-to-field isolation is available with external user-supplied power, selected by a wiring option on the IOTA

    All 32 outputs share a common return and take field power from one source: the Series 8 system supply or an external 24 V supply. An external source can isolate the outputs from the Series 8 power system. Each channel can be configured latched, pulsed, or pulse-width modulated, with direct or reverse action. Per-channel FAILOPT can hold the last value or shed to a user-defined safe value.

    Fused protection — do not assume the Series C “fuse-less” scheme

    Note 1 in section 4.4.10 states that short-circuit protection for a DO channel uses series fuses in the output channel, and that the DO IOTA carries four fuses for the 32 channels. That is a different protection style from Honeywell’s Series C bussed output CC-PDOB01, which is documented as fuse-less electronic shutoff and is also rated for a higher current (0.5 A per channel and 6 A per module). Do not treat 8C-PDODA1 as a current-rating equivalent of CC-PDOB01, and do not promise fuse-less behavior on this Series 8 IOP.

    When the IOTA or the relay extension is the part you actually need

    If the failed hardware is the 9-inch termination, the IOTA code is 8C-TDODA1, not 8C-PDODA1. If the position is already a 12-inch redundant board, the IOTA is 8C-TDODB1 and takes two IOMs. Dry-contact or mixed-voltage loads may require the 15-inch 8C-SDOX01 relay extension (32 Form C contacts) cabled to the DO IOTA — that assembly has its own voltage and current table and should be quoted only when the bill of materials calls for it [TO CONFIRM].

    Related Series 8 digital output pages

    Pairing and contrast only. Related Items below must not be styled as H1.

    • 8C-TDODA1 — 9-inch non-redundant bussed 24 V DO IOTA
    • 8C-TDILA1 — Series 8 digital input termination (different function)
    • CC-PDOB01 — Series C 24 V bussed DO IOP (different platform and current ratings)

    FAQ

    How much current can each channel switch?
    The official detailed table allows 100 mA per channel and 3.2 A per module. Size the load against those maxima, not against Series C 0.5 A figures.

    Is the output source or sink?
    The detailed specification for 8C-PDODA1 lists output type as source. This page follows that table.

    Does redundancy require a special IOTA?
    Yes. Use 8C-TDODB1 for the 12-inch redundant termination. Switchover gap on the output is documented as 0 ms.

    Are the outputs fuse-less?
    No. Short-circuit protection is described as series fuses on the IOTA (four fuses for 32 channels).

    Is a price shown here?
    No. Request a quotation after the IOP, IOTA, and any relay extension are identified.

    Request a quote for 8C-PDODA1

    Include the module nameplate, the IOTA code (8C-TDODA1 or 8C-TDODB1), and whether 8C-SDOX01 is part of the loop. HKXY Instruments will confirm condition, inspection, packing, and lead time. We are not Honeywell.

    Contact: Vicky · 86-18086430982 · vicky@hkxytech.com
    TOWER 707-713 NATHAN ROAD MONGKOK KOWLOON HONGKONG

    Request quote for 8C-PDODA1

    Have any question, Please enter the form below and click the submit button.


    *
    *
    5 + 9 = ?
    Please enter the answer to the sum & Click Submit to verify your registration.
    CATEGORY AND TAGS:

    Honeywell

    Related Items

  • Product Categories

  • Why Us?

    1. 100% original product, 100% quality assurance.

    2. Varied payment methods.

    3.Safe & High-efficient shipping

  • Contact Us




    Contact: Vicky

    Mobile Phone: 86-18086430982
    Mail:vicky@hkxytech.com

    Address: TOWER 707-713 NATHAN ROAD MONGKOK KOWLOON HONGKONG